  • undefined

Intelligent alarm controller

The controller can display the working status of the connected detector, tap position, query alarm records, set working mode, and provide password services

Service Hotline:

Detailed description

1. Main features

• It can be connected to on-site detection probes using bus or branch line systems, with flexible and convenient configurations;

• The controller can display the working status of the connected detector, tap position, query alarm records, set working mode, and provide password services;

• Each channel independently sets the input signal type, range, and alarm value;

• Highlighted numbers display

• Installation of multiple gas mixtures

• Remote display and monitoring of gas concentration

• Can output 4-20mA signal, relay output

• Removable installation bracket, convenient and fast on-site installation

 

2. Technical performance

• Host capacity: It can connect 223 digital communication bus detectors and 32 4-20mA analog detector inputs, and both analog and digital channels can be used simultaneously.

• LCD: Resolution 320 * 240, 5.1 inches

• Processor: ARM7

• Gas detection: O2, EX, CO, H2S, CL2, etc

• Display method: You can choose to display 4 on each page or 14 on each page.

• Inspection interval: 0.1s

• Page change interval: 4s-14s (adjustable)

• Single channel display: can only monitor the gas concentration of a single transmitter.

• Online settings: The parameters, calibration, and zeroing of the bus transmitter can be set online.

• Switch output: If equipped with a relay control box, there are 32 configurable relays and 1 common relay. If equipped with an 8-way relay control board, it comes with 8 configurable relays and 1 common relay

• Real name input: can input the installation address of the device, Chinese characters, numbers, and letters.

• Data storage: can store over 3200 gas alarm and startup records, using a cyclic coverage storage method.

• Communication interface: 1 RS485 communication with the bus transmitter. One RS232 can be connected to 32 relay control boxes or connected to a computer to read the alarm records and parameters of the controller.

• Communication speed: 9600bps (default)

• Transmission distance: The maximum distance between the detector and the controller is ≤ 1000 meters

• Installation method: wall mounted

• System power supply: AC220V ± 15%, 50Hz ± 1%

• Power supply for transmitter: DC24V

• Working temperature: -10 ℃~50 ℃

• Environmental humidity: ≤ 30% RH

 

3. Selection guide for alarm transmitter

 

model

Detection object
(Molecular formula)

name

measuring range

Uncertainty

Principles of Analysis

Remarks

 

 

 

TR-1000

CO

Carbon monoxide detection probe

0~1000mol/mol

 

 

≤±5%F.S

 

 

electrochemistry

 

 

Online

C7H8

Toluene gas detection probe

0~10μmol/mol

NH3

Ammonia gas detection probe

0~10μmol/mol

HCHO

Formaldehyde gas detection probe

0~10μmol/mol

H2S

Hydrogen sulfide detection probe

0~1000mol/mol

CL2

Chlorine detection probe

0~20μmol/mol

H2

Hydrogen gas detection probe

0~100μmol/mol

HCL

Hydrogen chloride detection probe

0~50μmol/mol

C2H4

Ethylene detection probe

0~20μmol/mol

O3

Ozone detection probe

0~1000μmol/mol

HCL

Hydrogen cyanide detection probe

0~100μmol/mol

SO2

Sulfur dioxide detection probe

0~1000μmol/mol

NO

Nitric oxide detection probe

0~1000μmol/mol

NO2

Nitrogen dioxide detection probe

0~1000μmol/mol

HF

Hydrogen fluoride detection probe

0~10μmol/mol

F2

Fluorine gas detection probe

0~10μmol/mol

PH3

Phosphine detection probe

0~1000μmol/mol

C2H5OH

Ethanol gas detection probe

0~100μmol/mol

CLO2

Chlorine dioxide detection probe

0~10μmol/mol

CH3COOC2H5

Ethyl acetate detection probe

0~1000μmol/mol

TR-1022

Combustible gas

Gas detection probe

0~100%LEL

Catalytic combustion

TR-23

O2

Oxygen gas detection probe

0~25%

 

electrochemistry

TR-XX

Analog input

Split line controller

1 to 32 control channels

 

 

XX represents several control routes

TR-RS-XX

Digital input

Bus based input controller

Control from 1 channel to 256 channels

 

 

XX represents several control routes

 

Key words:

Flue gas analyzer, flue gas online monitoring, VOCS online monitoring, waste incineration online monitoring

Classification:


online message


Note: Please fill in the above information correctly so that we can feedback the processing results to you at the first time!


JNYQ-S-81 flue gas analyzer

The JNYQ-S-81 flue gas analyzer is a gas analyzer product independently developed for online gas analysis of environmental protection and industrial control sites both domestically and internationally. This analyzer is based on the principle of ultraviolet absorption spectroscopy technology and can measure the concentration of gases such as SO2, NO, NO2, O2, etc. It has the characteristics of high measurement accuracy, high reliability, fast response time, and wide applicability. Its various indicators meet or exceed similar products at home and abroad, and can be widely used in environmental online monitoring, industrial control, safety monitoring, and other occasions.


TR-9100 Cement Process Gas Online Analysis System

The TR-9100 system is a gas composition analysis safety interlock device specially designed for the safe operation of cement plants. A solution provided based on targeted design using the mature analysis and control technology and sampling pretreatment technology of JuNeng Company to address the harsh working conditions of cement plants in China. Especially with the use of technologically innovative sampling probes with minimal maintenance, they are more suitable for the harsh working conditions of high dust cement in China.


TR-9300A miniature air quality monitoring system

The TR-9300A miniature environmental air quality monitoring system adopts light scattering and high-precision electrochemical detection technology. It is a high-performance sensing and collection device that integrates air six parameter monitoring (PM2.5, PM10, SO2, NO2, O3, CO), GPS positioning, and 4G communication. It has high integration, strong scalability, easy installation, and high sensitivity and reliability. It can be deployed in a grid form in various areas such as urban residential areas, business and office areas, industrial parks, transportation roads, and construction sites, to continuously monitor the air quality of the target area 24/7, providing basic data for comprehensive evaluation of urban air quality.


TR-9300D flue gas ultra-low emission continuous monitoring system

Xi'an Juneng Instrument Co., Ltd. has successfully launched the TR-9300D ultra-low emission continuous monitoring system for flue gas, based on years of research and application experience in environmental monitoring systems. The system is based on relevant standards and specifications such as HJ/T76-2007 and HJ/T75-2007. The analytical instrument used is the JNYQ-S-81 flue gas analyzer independently developed by Xi'an Juneng Instrument Co., Ltd. A single monitoring system adopts an architecture mode of monitoring platform probe+preprocessing+industrial computer+LCD display+data acquisition instrument to complete the functional requirements of receiving, storing, displaying, and transmitting monitoring data.


JNYQ-I-41 infrared gas analyzer

A new type of infrared gas analyzer designed and manufactured using the principle of non dispersive infrared for infrared analysis instruments


JNYQ-I-44Ex infrared gas analyzer

The JNYQ-I-44Ex model has an explosion-proof structure, which can be safely and reliably used in petroleum refining, chemical industry, natural gas, and other flammable and explosive environments